Technical data:
General |
Standards |
IEC/EN 60947 |
Climatic proofing |
Damp heat, constant,,
to IEC 60068-2-78
Damp heat, cyclic.
to IEC 60068-2-30 |
Ambient temperature |
-25 / +70 |
Mounting position |
As required |
Degree of protection |
IP66. IP65 for "T" Type with rubber strain |
Contacts/switching capacity |
Rated impulse withstand voltage |
Uimp |
VAC |
4000 |
Rated insulation voltage |
Ui |
V |
400 |
Overvolatge category/pollution degree |
III/3 |
Rated operational current |
AC-15 |
24V |
Ie |
A |
6 |
230V/240V |
Ie |
A |
6 |
400V/415V |
Ie |
A |
4 |
DC-13 |
24V |
Ie |
A |
10 |
110V |
Ie |
A |
1 |
220V |
Ie |
A |
0.5 |
Control circuit reliability |
at 24V |
DC / 5mA |
HF |
Fault probability |
<10-7,<1 failure at 107 operations |
at 5V |
DC / 1mA |
HF |
Fault probability |
<10-6,<1 failure at 5x106 operations |
Supply frequency |
Hz |
max. 400 |
Short-circuit rating in the closed state (IEC / EN 60947-5-1) |
Fuseless |
Type |
PKZM0-10 FAZ-B6/1 |
Max. Fuseless |
A gG / gL |
10 |
Short-circuit rating to IEC / EN 60947-5-1 |
Max. Fuseless |
A gG / gL |
6 |
Repetition accuracy |
mm |
0.02 |
|
|
|
|